Description: Operating power protection devices can be categorized into two types: DC power supply operation and AC operation. AC operating power is favored due to its lower investment costs, simpler operation, and reliable secondary circuit maintenance, making it widely used in small factories.
The direct-action protection circuit employs a manually operated mechanism within the overcurrent release (trip coil) YR, functioning as a direct-acting overcurrent relay. This relay is connected in a two-phase configuration or as a two-relay device type. During normal operation, the current through YR is significantly lower than the operating current, resulting in no action. In the event of a second-phase short circuit, YR activates to trip the circuit breaker QF. This operational mode is economically simple but offers low sensitivity and is rarely utilized.
In contrast, the shunt trip protection circuit operates differently. During normal operation, the current relay KA's normally closed contact shorts the trip coil YR. Consequently, YR does not trip the circuit breaker QF. When a phase short circuit occurs in the primary circuit, the current relay KA activates, opening the normally closed contacts and disconnecting the short-circuit trip coil YR from the current. This process, referred to as "de-streaming," allows the secondary current from the current transformer to flow entirely through YR, which then trips the circuit breaker QF, a process known as "de-shunt trip." This wiring method is relatively straightforward, reliable, and sensitive, although it requires that the breaking contacts of the current relay KA have sufficient capacity. Current relays such as GL15, GL16, and GL25, GL26 available on the market have large capacity contacts, capable of handling short break currents up to 150A, thus meeting the requirements for the shunt trip operation. As a result, this operational mode is widely implemented in power supply systems within factories.
The schematic design of these protection circuits involves integrating the trip coil YR with the circuit breaker QF and the current relay KA. The direct-action circuit requires a simple connection where the relay YR is directly linked to the overcurrent release mechanism, allowing for manual reset after tripping. In the shunt trip circuit, the current relay KA must be positioned to ensure it can effectively disconnect the trip coil YR when a fault occurs. The connection between the current transformer and YR must be designed to handle the expected load currents, ensuring that the sensitivity of the protection mechanism is adequate to detect faults without nuisance tripping.
In summary, the design considerations for these protection circuits focus on ensuring reliability, sensitivity, and the ability to handle fault conditions while maintaining ease of operation and cost-effectiveness, particularly in small factory environments. The choice between direct-action and shunt trip methods is influenced by the specific requirements of the application, including sensitivity to faults and the operational characteristics of the electrical system.Operating power protection devices, there is a DC power supply operating power and AC operation into two categories. Since the AC operating power with less investment, operation and maintenance is simple and convenient and reliable secondary circuit, so it is widely used in small factories. (1) Direct-action protection circuit uses off circuit breaker manually operated mechanism within the overcurrent release (trip coil) YR as a direct-acting overcurrent relay , a relay connected into a two-phase or two-phase two-relay device type.
During normal operation, the current YR by far less than the operating current, and therefore no action. In a second phase short circuit when the circuit, YR movements to trip the circuit breaker QF, this mode of operation is simple by economic, but the protection of low sensitivity, in fact seldom used, as shown in FIG.
(2) to shunt trip protection circuit shown in Figure b. Normal operation, the current relay KA normally closed contact will short-circuit trip coil YR stream. YR no current through the circuit breaker QF is not so trips. When the primary circuit phase short circuit, the current relay KA action, the normally closed contacts disconnect, short-circuit trip coil YR partial stream branch is removed, the so-called "de-streaming", so that the current transformer secondary current all through YR, QF causing the circuit breaker tripped, the so-called "de-shunt trip." Wiring this mode of operation is relatively simple, reliable and sensitive, but requires current relay KA breaking contacts can force big enough.
GL15,16 on the market and other types of GL25,26 current relay, which contacts a large capacity, short break current unitary division of 150A, fully able to meet short circuit "to shunt trip" requirements. Therefore, this mode of operation to shunt trip power supply system in the factory now applied quite widely.
A time delay relay is a relay that remains activated for a specific duration after being triggered. This type of relay consists of a straightforward adjustable timer circuit that regulates the operation of the relay. The timing can be adjusted...
An NPN bipolar transistor is typically utilized for relay switching, particularly with 12V coil-rated relays, as it helps maintain circuit separation. A diode is also added to prevent issues. The necessity of driving the relay with a transistor depends on...
The physical location of the compressor relay is needed, as well as instructions on how to test the pressure sensor on the plastic tank of the compressor assembly. The exact location of the relay has not been confirmed, but one...
When utilizing a regulated power supply to decrease voltage, there exists a risk of component failure within the supply, potentially resulting in damage to connected equipment. While a fuse can provide protection against excessive current draw, it may not respond...
Although this may be a basic question, there is still some struggle with it. In this schematic, two zener diodes D1 and D2 are connected back-to-back across relay coil L1. The breakdown voltage (BVds) is -30V for Q1. The question...
A relay is activated by grounding the low side using an NPN transistor. A pushbutton is intended to operate the transistor, thereby energizing the relay for approximately 500 milliseconds before deactivating it, while ignoring any continuous button press. Although timers...
The Spartan-3 board features external 5V relay interfacing, as depicted in the accompanying figure. The ULN2803 is utilized as a driver for the FPGA I/O lines, with the driver outputs connected to the relay modules. A PTB connector is provided...
DC power supply with a shunt, rectifier, filter, limiter, and regulator. The circuit is simple and cost-effective, capable of meeting the requirements. The 6.3V indicator lights HL1 and HL2 indicate the lathe's running and stopping status through a relay control...
This circuit turns on a relay when two buttons are pressed at the same time. The relay backs off after a few seconds, then the buttons have to be released and pressed again. This feature is often required in industrial...
We use cookies to enhance your experience, analyze traffic, and (if you allow) serve personalized ads.
By clicking Accept All, you agree to our use of cookies.
Learn more